HomeProjectsEV Charger via Augmented Load Calculation — Delta
EV Charger Installation

EV Charger via Augmented Load Calculation — Delta

A conventional load calculation said the service had no capacity. Using Technical Safety BC's augmented method with 12 months of real BC Hydro usage data, the home supported a 40-amp circuit after all — no service upgrade needed.

EV Charger via Augmented Load Calculation — Delta — Delta, BC · EV Charger Installation case study by ElectroMax
Location
Delta, BC
Service
EV Charger Installation
Tags
ChargePoint, Augmented Load Calculation, No Service Upgrade
Challenge

A homeowner in Delta wanted an EV charger installed, but a conventional electrical load calculation indicated that their existing service did not have enough available capacity. They contacted ElectroMax Systems to assess their options.

Solution

Following the method outlined in Technical Safety BC's EV charging bulletin, we obtained the home's previous 12 months of BC Hydro electricity usage data and completed an augmented load calculation. This assessment showed that the home's actual electrical demand left sufficient capacity for an EV charger on a 40-amp circuit breaker, with the charger limited to 32 amps. Using the calculation to support the electrical permit application, we obtained the permit from Technical Safety BC and completed the installation. We applied the required identification labels to the electrical panel and a current-limit label to the charger documenting its 32-amp setting.

Outcome

The installation passed its final electrical inspection. The homeowner received a permitted and inspected EV charging installation without needing a service upgrade — supported by an assessment of the home's actual electrical demand. We then provided the customer with the paid invoice, electrical permit documentation, and supporting paperwork for their rebate application.